Small coal-fired power plant generator bearing general provisions?

1,during normal operation,the generator of lubricating oil inlet temperature and pressure shall be controlled according to the manufacturer.2,the side of the steam turbine generator exciter and exciter bearing,bearing should be and the casing electrical motor 12v 1000w insulating (best in between two layers of insulation pad with metal plate,in order to measure the insulation).3,when produced in the steam turbine generator rotor of high electrostatic voltage,the mother should gasoline generator spare parts be near the worm wheel on the side of the shaft grounding device brush,generally after 100~300 grounding resistance.4,on each tubing shall be installed two of the insulation flange,so that the generator runtime checking tubing insulation condition.In all tubing low speed permanent magnet generatorinstalled,the insulation of the steam turbine generator and exciter bearing resistance with 1000 v,shaking table,the measurement shall not be less than 1 m Ω.5,steam turbine generator and exciter bearing,should be made it impossible for oil splash to the coil,the slip ring and the commutator.